Water quality report for Emory, TX — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.
A look at Emory's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.
Lead was not detected. No PFAS was detected.
Graded on violations, lead, and PFAS, with state inspection findings.
| Contaminant | Type | Measured | Limit | Period | Status |
|---|---|---|---|---|---|
| TTHM | MCL EXCEEDANCE | 0.093 MG/L | 0.080 mg/L | 2026 | Unaddressed |
| TTHM | MCL EXCEEDANCE | 0.094 MG/L | 0.080 mg/L | 2026 | Unaddressed |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.069 MG/L | 0.060 mg/L | 2026 | Unaddressed |
| Public Notice | OTHER | — | — | 2026 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.094 MG/L | 0.080 mg/L | 2026 | Archived |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.069 MG/L | 0.060 mg/L | 2026 | Archived |
| TTHM | MCL EXCEEDANCE | 0.092 MG/L | 0.080 mg/L | 2025 | Archived |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.069 MG/L | 0.060 mg/L | 2025 | Archived |
| Revised Total Coliform Rule | MONITORING FAILURE | — | — | 2025 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.087 MG/L | 0.080 mg/L | 2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.093 MG/L | 0.080 mg/L | 2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.091 MG/L | 0.080 mg/L | 2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.09 MG/L | 0.080 mg/L | 2024 | Archived |
| Revised Total Coliform Rule | MONITORING FAILURE | — | — | 2024 | Resolved |
| Public Notice | OTHER | — | — | 2021 | Resolved |
| Public Notice | OTHER | — | — | 2020 | Resolved |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2019 | Resolved |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2018 | Resolved |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2018 | Resolved |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2017 | Resolved |
| Public Notice | OTHER | — | — | 2017 | Resolved |
| Consumer Confidence Rule | OTHER | — | — | 2017 | Resolved |
| Public Notice | OTHER | — | — | 2016 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | MONITORING AND REPORTING | — | — | 2016 | Resolved |
| CARBON, TOTAL | MONITORING AND REPORTING | — | TT | 2016 | Archived |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2016 | Resolved |
| Lead and Copper Rule | MONITORING AND REPORTING | — | TT | 2016 | Resolved |
| Revised Total Coliform Rule | MONITORING FAILURE | — | — | 2016 | Resolved |
| Coliform (TCR) | MONITORING AND REPORTING | — | 5% of samples | 2016 | Resolved |
| Coliform (TCR) | MCL EXCEEDANCE | — | 5% of samples | 2016 | Resolved |
| Public Notice | OTHER | — | — | 2016 | Resolved |