Water quality report for Black Lick, PA — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.
A look at Black Lick's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.
Lead is 1.93 ppb, 13% of the action level and no violations are open. No PFAS was detected.
Graded on violations, lead, and PFAS, with state inspection findings.
| Contaminant | Type | Measured | Limit | Period | Status |
|---|---|---|---|---|---|
| Public Notice | OTHER | — | — | 2025 | Resolved |
| Simazine | MONITORING AND REPORTING | — | 0.004 mg/L | 2025 | Resolved |
| Atrazine | MONITORING AND REPORTING | — | 0.003 mg/L | 2025 | Resolved |
| 2,4-D | MONITORING AND REPORTING | — | 0.07 mg/L | 2025 | Resolved |
| Total Haloacetic Acids (HAA5) | MONITORING AND REPORTING | — | 0.060 mg/L | 2024 | Resolved |
| Surface Water Treatment Rule | MONITORING AND REPORTING | — | — | 2023 | Resolved |
| Total Haloacetic Acids (HAA5) | MONITORING AND REPORTING | — | 0.060 mg/L | 2023 | Resolved |
| Selenium | MONITORING AND REPORTING | — | 0.05 mg/L | 2023 | Resolved |
| Arsenic | MONITORING AND REPORTING | — | 0.010 mg/L | 2021 | Resolved |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.075 MG/L | 0.060 mg/L | 2020 | Resolved |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.063 MG/L | 0.060 mg/L | 2019 | Resolved |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.074 MG/L | 0.060 mg/L | 2019 | Resolved |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.075 MG/L | 0.060 mg/L | 2019 | Resolved |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.066 MG/L | 0.060 mg/L | 2019 | Resolved |