States ›Louisiana ›Union Parish ›Downsville

Downsville, LA Tap Water Quality 2026

Water quality report for Downsville, LA — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.

A look at Downsville's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.

Main Utility: Village Of Downsville Water System PWSID: LA1111004 Updated: 2026 Q2
✅

No federal limits exceeded on record

Lead is 2.00 ppb, 13% of the action level and no violations are open. PFAS has never been sampled at this system.

B

Downsville earns a B for water quality

Graded on violations and lead, with state inspection findings. PFAS not tested.

Lead: 2.00 ppb — 13% of the federal action level
PFAS never sampled at this system
64 violations since 2015, 49 health-based
No violations currently open
Downsville's lead level vs. all Louisiana community water systems
0 ppb5 ppb10 ppb15 ppb
Lead level: 2.00 ppb — 13% of the federal action level
✓ Lower lead than 56% of Louisiana utilities
Population Served
96
~72 connections
Water Source
Groundwater
Drawn from wells — SDWIS source code GW
Active Violations
0
64 since 2015, all resolved

Lead & Copper Testing

Lead (Pb)
90th percentile of tap samples collected across the distribution system
13% of EPA action level
2.00 ppb
Action level: 15 ppb
The 90th-percentile lead result is 2.00 ppb, 13% of the 15 ppb federal action level. The action level is a treatment trigger, not a legal maximum, and it is measured across sampled taps rather than at any single home.

Contaminant Violations (2015–Present)

ContaminantTypeMeasuredLimitPeriodStatus
Public Notice OTHER — — 2025 Resolved
TTHM MCL EXCEEDANCE 0.09 MG/L 0.080 mg/L 2025 Archived
TTHM MCL EXCEEDANCE 0.104 MG/L 0.080 mg/L 2025 Archived
TTHM MCL EXCEEDANCE 0.099 MG/L 0.080 mg/L 2025 Archived
TTHM MCL EXCEEDANCE 0.097 MG/L 0.080 mg/L 2024 Archived
TTHM MCL EXCEEDANCE 0.101 MG/L 0.080 mg/L 2024 Archived
TTHM MCL EXCEEDANCE 0.086 MG/L 0.080 mg/L 2024 Archived
TTHM MCL EXCEEDANCE 0.093 MG/L 0.080 mg/L 2024 Archived
TTHM MCL EXCEEDANCE 0.088 MG/L 0.080 mg/L 2023 Archived
TTHM MCL EXCEEDANCE 0.089 MG/L 0.080 mg/L 2023 Archived
TTHM MCL EXCEEDANCE 113 UG/L 0.080 mg/L 2023 Archived
TTHM MCL EXCEEDANCE 0.09 MG/L 0.080 mg/L 2023 Archived
TTHM MCL EXCEEDANCE 0.095 MG/L 0.080 mg/L 2022 Archived
TTHM MCL EXCEEDANCE 0.094 MG/L 0.080 mg/L 2022 Archived
TTHM MCL EXCEEDANCE 0.095 MG/L 0.080 mg/L 2022 Archived
TTHM MCL EXCEEDANCE 0.099 MG/L 0.080 mg/L 2022 Archived
TTHM MCL EXCEEDANCE 0.095 MG/L 0.080 mg/L 2021 Archived
TTHM MCL EXCEEDANCE 0.109 MG/L 0.080 mg/L 2021 Archived
TTHM MCL EXCEEDANCE 0.115 MG/L 0.080 mg/L 2021 Archived
TTHM MCL EXCEEDANCE 0.117 MG/L 0.080 mg/L 2021 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.073 MG/L 0.060 mg/L 2021 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.086 MG/L 0.060 mg/L 2020 Archived
TTHM MCL EXCEEDANCE 0.121 MG/L 0.080 mg/L 2020 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.077 MG/L 0.060 mg/L 2020 Archived
TTHM MCL EXCEEDANCE 0.123 MG/L 0.080 mg/L 2020 Archived
Public Notice OTHER — — 2020 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.089 MG/L 0.060 mg/L 2020 Archived
TTHM MCL EXCEEDANCE 0.141 MG/L 0.080 mg/L 2020 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.092 MG/L 0.060 mg/L 2020 Archived
TTHM MCL EXCEEDANCE 0.145 MG/L 0.080 mg/L 2020 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.094 MG/L 0.060 mg/L 2019 Archived
TTHM MCL EXCEEDANCE 0.144 MG/L 0.080 mg/L 2019 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.096 MG/L 0.060 mg/L 2019 Archived
TTHM MCL EXCEEDANCE 0.137 MG/L 0.080 mg/L 2019 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.074 MG/L 0.060 mg/L 2019 Archived
TTHM MCL EXCEEDANCE 0.105 MG/L 0.080 mg/L 2019 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.066 MG/L 0.060 mg/L 2019 Archived
TTHM MCL EXCEEDANCE 0.091 MG/L 0.080 mg/L 2019 Archived
TTHM MCL EXCEEDANCE 0.092 MG/L 0.080 mg/L 2018 Archived
TTHM MCL EXCEEDANCE 93 UG/L 0.080 mg/L 2018 Archived
TTHM MCL EXCEEDANCE 113 UG/L 0.080 mg/L 2018 Archived
Groundwater Rule TREATMENT TECHNIQUE — — 2018 Resolved
TTHM MCL EXCEEDANCE 125 UG/L 0.080 mg/L 2018 Archived
TTHM MONITORING AND REPORTING — 0.080 mg/L 2017 Resolved
Consumer Confidence Rule OTHER — — 2017 Resolved
TTHM MCL EXCEEDANCE 116 UG/L 0.080 mg/L 2017 Archived
TTHM MONITORING AND REPORTING — 0.080 mg/L 2017 Resolved
TTHM MCL EXCEEDANCE 113 UG/L 0.080 mg/L 2017 Archived
TTHM MCL EXCEEDANCE 87 UG/L 0.080 mg/L 2017 Archived
TTHM MONITORING AND REPORTING — 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2016 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 86 UG/L 0.080 mg/L 2016 Archived
TTHM MCL EXCEEDANCE 112 UG/L 0.080 mg/L 2016 Archived
TTHM MCL EXCEEDANCE 134 UG/L 0.080 mg/L 2016 Archived
TTHM MCL EXCEEDANCE 128 UG/L 0.080 mg/L 2015 Archived
TTHM MONITORING AND REPORTING — 0.080 mg/L 2015 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2015 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2015 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2015 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2015 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2015 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2015 Resolved
TTHM MCL EXCEEDANCE 91 UG/L 0.080 mg/L 2015 Archived
Understanding violation types MCL violations mean a contaminant exceeded the federal maximum limit — the most serious type.
TT (Treatment Technique) violations mean required treatment procedures weren't followed, but don't necessarily mean contamination occurred.

Violation History

64 violations are on record since 2015, of which 49 were health-based. All have been resolved and none remain open.

About the Main Water System

Utility Village Of Downsville Water System
PWSID LA1111004
Water source Groundwater — Drawn from wells — SDWIS source code GW
Population served 96
Service connections 72
Systems serving this area 1
Regulator State primacy agency
Data through 2026 Q2 — EPA SDWIS

Frequently Asked Questions

Is Downsville tap water safe to drink? ▼
No federal limit is exceeded on record. No violations are currently open. Lead is 2.00 ppb, 13% of the action level.
Does Downsville water have PFAS? ▼
This system has never been sampled for PFAS. EPA's national monitoring covered systems serving 3,300 people or more, so no results exist — which is not evidence that none is present.
Who supplies water to Downsville? ▼
Village Of Downsville Water System (PWSID LA1111004). Groundwater. Drawn from wells — SDWIS source code GW
When was this system last inspected? ▼
It was last inspected on 2026-03-09. No significant deficiencies were recorded.

What Should Downsville Residents Do?

1
Read your annual water report
Your supplier publishes a Consumer Confidence Report each July covering the prior year.
2
Check for a lead service line
Lead reaches tap water mainly through service lines and household plumbing. Suppliers now publish an inventory identifying lead lines.
3
Flush before drinking
If water has sat in pipes more than six hours, run the cold tap for two minutes before drinking or cooking.

Nearby Cities in Louisiana

Farmerville, La Tap Water Quality 2026 Union Parish Bernice, La Tap Water Quality 2026 Union Parish Marion, La Tap Water Quality 2026 Union Parish Junction City, La Tap Water Quality 2026 Union Parish Spearsville, La Tap Water Quality 2026 Union Parish Lillie, La Tap Water Quality 2026 Union Parish