Powhatan, LA Tap Water Quality 2026

Water quality report for Powhatan, LA — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.

A look at Powhatan's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.

Main Utility: Sabine Parish Wd #1 - Powhatan PWSID: LA1069008 Updated: 2026 Q2
🚨

1 violation currently open

Lead is 1.00 ppb, 7% of the action level. PFAS has never been sampled at this system.

D

Powhatan earns a D for water quality

Graded on violations and lead, with state inspection findings. PFAS not tested.

Lead: 1.00 ppb — 7% of the federal action level
PFAS never sampled at this system
54 violations since 2015, 31 health-based
1 violation currently open
Powhatan's lead level vs. all Louisiana community water systems
0 ppb5 ppb10 ppb15 ppb
Lead level: 1.00 ppb — 7% of the federal action level
✓ Lower lead than 88% of Louisiana utilities
Population Served
99
~204 connections
Water Source
Groundwater
Drawn from wells — SDWIS source code GW
Active Violations
1
1 open of 54 since 2015

Lead & Copper Testing

Lead (Pb)
90th percentile of tap samples collected across the distribution system
7% of EPA action level
1.00 ppb
Action level: 15 ppb
The 90th-percentile lead result is 1.00 ppb, 7% of the 15 ppb federal action level. The action level is a treatment trigger, not a legal maximum, and it is measured across sampled taps rather than at any single home.

Contaminant Violations (2015–Present)

ContaminantTypeMeasuredLimitPeriodStatus
Groundwater Rule TREATMENT TECHNIQUE — — 2023 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2023 Unaddressed
TTHM MCL EXCEEDANCE 0.084 MG/L 0.080 mg/L 2022 Resolved
Public Notice OTHER — — 2022 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.081 MG/L 0.060 mg/L 2022 Resolved
TTHM MCL EXCEEDANCE 0.107 MG/L 0.080 mg/L 2022 Resolved
Public Notice OTHER — — 2022 Resolved
TTHM MCL EXCEEDANCE 0.145 MG/L 0.080 mg/L 2022 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.148 MG/L 0.060 mg/L 2022 Resolved
Public Notice OTHER — — 2021 Unaddressed
Public Notice OTHER — — 2021 Resolved
Public Notice OTHER — — 2021 Resolved
TTHM MCL EXCEEDANCE 0.176 MG/L 0.080 mg/L 2021 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.162 MG/L 0.060 mg/L 2021 Resolved
Public Notice OTHER — — 2021 Resolved
Lead and Copper Rule MONITORING AND REPORTING — TT 2021 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.161 MG/L 0.060 mg/L 2021 Resolved
TTHM MCL EXCEEDANCE 0.171 MG/L 0.080 mg/L 2021 Resolved
TTHM MCL EXCEEDANCE 0.128 MG/L 0.080 mg/L 2021 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.128 MG/L 0.060 mg/L 2021 Resolved
Public Notice OTHER — — 2020 Addressed
Groundwater Rule TREATMENT TECHNIQUE — — 2020 Addressed
Groundwater Rule TREATMENT TECHNIQUE — — 2020 Addressed
Public Notice OTHER — — 2020 Unaddressed
Public Notice OTHER — — 2020 Addressed
Public Notice OTHER — — 2019 Addressed
Revised Total Coliform Rule TREATMENT TECHNIQUE — — 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Public Notice OTHER — — 2019 Addressed
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Addressed
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Addressed
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
E. COLI MONITORING AND REPORTING — 0 2019 Resolved
Groundwater Rule TREATMENT TECHNIQUE — — 2019 Resolved
Public Notice OTHER — — 2019 Unaddressed
Revised Total Coliform Rule TREATMENT TECHNIQUE — — 2018 Resolved
Consumer Confidence Rule OTHER — — 2017 Resolved
TTHM MCL EXCEEDANCE 91 UG/L 0.080 mg/L 2017 Resolved
Public Notice OTHER — — 2016 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 104 UG/L 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2016 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 104 UG/L 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 66 UG/L 0.060 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 138 UG/L 0.080 mg/L 2016 Resolved
Public Notice OTHER — — 2016 Resolved
TTHM MONITORING AND REPORTING — 0.080 mg/L 2015 Resolved
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2015 Resolved
Understanding violation types MCL violations mean a contaminant exceeded the federal maximum limit — the most serious type.
TT (Treatment Technique) violations mean required treatment procedures weren't followed, but don't necessarily mean contamination occurred.

Violation History

1 violation remains open, out of 54 recorded since 2015 (31 health-based).

About the Main Water System

Utility Sabine Parish Wd #1 - Powhatan
PWSID LA1069008
Water source Groundwater — Drawn from wells — SDWIS source code GW
Population served 99
Service connections 204
Systems serving this area 1
Regulator State primacy agency
Data through 2026 Q2 — EPA SDWIS

Frequently Asked Questions

Is Powhatan tap water safe to drink? ▼
No federal limit is exceeded on record. 1 violation(s) remain open. Lead is 1.00 ppb, 7% of the action level.
Does Powhatan water have PFAS? ▼
This system has never been sampled for PFAS. EPA's national monitoring covered systems serving 3,300 people or more, so no results exist — which is not evidence that none is present.
Who supplies water to Powhatan? ▼
Sabine Parish Wd #1 - Powhatan (PWSID LA1069008). Groundwater. Drawn from wells — SDWIS source code GW
When was this system last inspected? ▼
It was last inspected on 2024-05-09. No significant deficiencies were recorded.

What Should Powhatan Residents Do?

1
Read your annual water report
Your supplier publishes a Consumer Confidence Report each July covering the prior year.
2
Check for a lead service line
Lead reaches tap water mainly through service lines and household plumbing. Suppliers now publish an inventory identifying lead lines.
3
Follow the open violation
This system has an unresolved violation. Contact the supplier for its corrective-action schedule.

Nearby Cities in Louisiana

Natchitoches, La Tap Water Quality 2026 Natchitoches Parish Vienna Bend, La Tap Water Quality 2026 Natchitoches Parish Campti, La Tap Water Quality 2026 Natchitoches Parish Provencal, La Tap Water Quality 2026 Natchitoches Parish Point Place, La Tap Water Quality 2026 Natchitoches Parish Natchez, La Tap Water Quality 2026 Natchitoches Parish