Water quality report for Thomson, GA — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.
A look at Thomson's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.
Lead is 2.10 ppb, 14% of the action level and no violations are open. No PFAS was detected.
Graded on violations, lead, and PFAS, with state inspection findings.
| Contaminant | Type | Measured | Limit | Period | Status |
|---|---|---|---|---|---|
| TTHM | MCL EXCEEDANCE | 0.111 MG/L | 0.080 mg/L | 2026 | Archived |
| TTHM | MCL EXCEEDANCE | 0.113 MG/L | 0.080 mg/L | 2025 | Archived |
| Total Haloacetic Acids (HAA5) | MCL EXCEEDANCE | 0.061 MG/L | 0.060 mg/L | 2025 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.102 MG/L | 0.080 mg/L | 2025 | Archived |
| Revised Total Coliform Rule | MONITORING FAILURE | — | — | 2025 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.104 MG/L | 0.080 mg/L | 2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.095 MG/L | 0.080 mg/L | 2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.09 MG/L | 0.080 mg/L | 2024 | Archived |
| Revised Total Coliform Rule | MONITORING FAILURE | — | — | 2024 | Resolved |
| Consumer Confidence Rule | OTHER | — | — | 2024 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.092 MG/L | 0.080 mg/L | 2024 | Archived |
| TTHM | MCL EXCEEDANCE | 0.092 MG/L | 0.080 mg/L | 2024 | Resolved |
| Revised Total Coliform Rule | REPORTING FAILURE | — | — | 2023 | Resolved |
| Revised Total Coliform Rule | REPORTING FAILURE | — | — | 2023 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.085 MG/L | 0.080 mg/L | 2023 | Resolved |
| Revised Total Coliform Rule | REPORTING FAILURE | — | — | 2023 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.091 MG/L | 0.080 mg/L | 2023 | Resolved |
| Revised Total Coliform Rule | REPORTING FAILURE | — | — | 2023 | Resolved |
| Public Notice | OTHER | — | — | 2022 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.099 MG/L | 0.080 mg/L | 2022 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.095 MG/L | 0.080 mg/L | 2022 | Resolved |
| Consumer Confidence Rule | OTHER | — | — | 2022 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.09 MG/L | 0.080 mg/L | 2022 | Resolved |
| Consumer Confidence Rule | OTHER | — | — | 2021 | Resolved |
| Consumer Confidence Rule | OTHER | — | — | 2020 | Resolved |
| Gross Alpha, Excl. Radon and U | MONITORING AND REPORTING | — | 15 pCi/L | 2017–2025 | Archived |
| Combined Uranium | MONITORING AND REPORTING | — | 30 ug/L | 2017–2025 | Archived |
| Combined Radium (-226 and -228) | MONITORING AND REPORTING | — | 5 pCi/L | 2017–2025 | Archived |
| Gross Alpha, Excl. Radon and U | MONITORING AND REPORTING | — | 15 pCi/L | 2017–2025 | Archived |
| Combined Uranium | MONITORING AND REPORTING | — | 30 ug/L | 2017–2025 | Archived |
| Combined Radium (-226 and -228) | MONITORING AND REPORTING | — | 5 pCi/L | 2017–2025 | Archived |
| TTHM | MCL EXCEEDANCE | 0.085 MG/L | 0.080 mg/L | 2016 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.082 MG/L | 0.080 mg/L | 2015 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.084 MG/L | 0.080 mg/L | 2015 | Resolved |
| TTHM | MCL EXCEEDANCE | 0.086 MG/L | 0.080 mg/L | 2015 | Resolved |