States ›Georgia ›Lowndes County ›Remerton

Remerton, GA Tap Water Quality 2026

Water quality report for Remerton, GA — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.

A look at Remerton's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.

Main Utility: Valdosta PWSID: GA1850002 Updated: 2026 Q2
✅

No federal limits exceeded on record

Lead was not detected and no violations are open. PFAS was detected below the federal limit.

B

Remerton earns a B for water quality

Graded on violations, lead, and PFAS, with state inspection findings.

Lead: not detected
PFAS detected below the federal limit
20 violations since 2015, 16 health-based
No violations currently open
Remerton's lead level vs. all Georgia community water systems
0 ppb5 ppb10 ppb15 ppb
Lead level: Not detected — 0% of the federal action level
✓ Lower lead than % of Georgia utilities
Population Served
665
~21830 connections
Water Source
Groundwater
Drawn from wells — SDWIS source code GW
Active Violations
0
20 since 2015, all resolved

Lead & Copper Testing

Lead (Pb)
90th percentile of tap samples collected across the distribution system
0% of EPA action level
Not detected
Action level: 15 ppb
Lead was not detected at the 90th percentile — the result fell below the laboratory detection limit. That is not the same as an absence of lead in every tap, and older homes with lead service lines can still show higher readings.

Contaminant Violations (2015–Present)

ContaminantTypeMeasuredLimitPeriodStatus
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.066 MG/L 0.060 mg/L 2026 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.07 MG/L 0.060 mg/L 2025 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.072 MG/L 0.060 mg/L 2025 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.066 MG/L 0.060 mg/L 2025 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.064 MG/L 0.060 mg/L 2025 Archived
TTHM MCL EXCEEDANCE 0.084 MG/L 0.080 mg/L 2025 Resolved
Lead and Copper Rule MONITORING AND REPORTING — TT 2023 Resolved
Consumer Confidence Rule OTHER — — 2022 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.061 MG/L 0.060 mg/L 2021 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.062 MG/L 0.060 mg/L 2021 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.066 MG/L 0.060 mg/L 2018 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.061 MG/L 0.060 mg/L 2018 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.064 MG/L 0.060 mg/L 2017 Resolved
Consumer Confidence Rule OTHER — — 2016 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.062 MG/L 0.060 mg/L 2015 Resolved
Coliform (TCR) MCL EXCEEDANCE — 5% of samples 2015 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.073 MG/L 0.060 mg/L 2015 Resolved
Coliform (TCR) MONITORING AND REPORTING — 5% of samples 2015 Archived
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.081 MG/L 0.060 mg/L 2015 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 0.074 MG/L 0.060 mg/L 2015 Resolved
Understanding violation types MCL violations mean a contaminant exceeded the federal maximum limit — the most serious type.
TT (Treatment Technique) violations mean required treatment procedures weren't followed, but don't necessarily mean contamination occurred.

Violation History

20 violations are on record since 2015, of which 16 were health-based. All have been resolved and none remain open.

About the Main Water System

Utility Valdosta
PWSID GA1850002
Water source Groundwater — Drawn from wells — SDWIS source code GW
Population served 665
Service connections 21,830
Systems serving this area 2
Regulator State primacy agency
Data through 2026 Q2 — EPA SDWIS

Frequently Asked Questions

Is Remerton tap water safe to drink? ▼
No federal limit is exceeded on record. No violations are currently open.
Does Remerton water have PFAS? ▼
PFAS was detected but stayed below the federal limit.
Who supplies water to Remerton? ▼
Valdosta (PWSID GA1850002), one of 2 systems serving this area. Groundwater. Drawn from wells — SDWIS source code GW
When was this system last inspected? ▼
It was last inspected on 2023-10-10. No significant deficiencies were recorded.

What Should Remerton Residents Do?

1
Read your annual water report
Your supplier publishes a Consumer Confidence Report each July covering the prior year.
2
Check for a lead service line
Lead reaches tap water mainly through service lines and household plumbing. Suppliers now publish an inventory identifying lead lines.
3
Flush before drinking
If water has sat in pipes more than six hours, run the cold tap for two minutes before drinking or cooking.