States ›Florida ›Sumter County ›Coleman

Coleman, FL Tap Water Quality 2026

Water quality report for Coleman, FL — PFAS, lead and copper results, violation history and state inspection findings from EPA SDWIS.

A look at Coleman's drinking water using EPA enforcement records: violations, lead and copper results, PFAS sampling and state inspection findings.

Main Utility: Coleman, City Of PWSID: FL6604861 Updated: 2026 Q2
✅

No federal limits exceeded on record

Lead is 4.70 ppb, 31% of the action level and no violations are open. PFAS has never been sampled at this system.

C

Coleman earns a C for water quality

Graded on violations and lead, with state inspection findings. PFAS not tested.

Lead: 4.70 ppb — 31% of the federal action level
PFAS never sampled at this system
17 violations since 2015, 16 health-based
No violations currently open
Coleman's lead level vs. all Florida community water systems
0 ppb5 ppb10 ppb15 ppb
Lead level: 4.70 ppb — 31% of the federal action level
✓ Lower lead than 7% of Florida utilities
Population Served
617
~386 connections
Water Source
Groundwater
Drawn from wells — SDWIS source code GW
Active Violations
0
17 since 2015, all resolved

Lead & Copper Testing

Lead (Pb)
90th percentile of tap samples collected across the distribution system
31% of EPA action level
4.70 ppb
Action level: 15 ppb
Copper (Cu)
90th percentile of tap samples. SDWIS reports a copper figure only when a system exceeds the action level, so any value here is an exceedance.
109.2% of EPA action level
1,420 ppb
Action level: 1,300 ppb
The 90th-percentile lead result is 4.70 ppb, 31% of the 15 ppb federal action level. The action level is a treatment trigger, not a legal maximum, and it is measured across sampled taps rather than at any single home. Copper reached the action level here; a copper figure appears in SDWIS only when a system triggers it.

Contaminant Violations (2015–Present)

ContaminantTypeMeasuredLimitPeriodStatus
Total Haloacetic Acids (HAA5) MONITORING AND REPORTING — 0.060 mg/L 2022 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 73.075 UG/L 0.060 mg/L 2020 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 69.85 UG/L 0.060 mg/L 2020 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 76.95 UG/L 0.060 mg/L 2020 Resolved
TTHM MCL EXCEEDANCE 83.8 UG/L 0.080 mg/L 2020 Resolved
TTHM MCL EXCEEDANCE 83.425 UG/L 0.080 mg/L 2019 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 73.55 UG/L 0.060 mg/L 2019 Resolved
TTHM MCL EXCEEDANCE 88.85 UG/L 0.080 mg/L 2019 Resolved
TTHM MCL EXCEEDANCE 109 UG/L 0.080 mg/L 2019 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 115 UG/L 0.060 mg/L 2019 Resolved
TTHM MCL EXCEEDANCE 89.5 UG/L 0.080 mg/L 2017 Resolved
TTHM MCL EXCEEDANCE 99.65 UG/L 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 62.425 UG/L 0.060 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 86.725 UG/L 0.080 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 74.95 UG/L 0.060 mg/L 2016 Resolved
Total Haloacetic Acids (HAA5) MCL EXCEEDANCE 73.225 UG/L 0.060 mg/L 2016 Resolved
TTHM MCL EXCEEDANCE 83.725 UG/L 0.080 mg/L 2016 Resolved
Understanding violation types MCL violations mean a contaminant exceeded the federal maximum limit — the most serious type.
TT (Treatment Technique) violations mean required treatment procedures weren't followed, but don't necessarily mean contamination occurred.

Violation History

17 violations are on record since 2015, of which 16 were health-based. All have been resolved and none remain open.

About the Main Water System

Utility Coleman, City Of
PWSID FL6604861
Water source Groundwater — Drawn from wells — SDWIS source code GW
Population served 617
Service connections 386
Systems serving this area 1
Regulator State primacy agency
Data through 2026 Q2 — EPA SDWIS

Frequently Asked Questions

Is Coleman tap water safe to drink? ▼
No federal limit is exceeded on record. No violations are currently open. Lead is 4.70 ppb, 31% of the action level.
Does Coleman water have PFAS? ▼
This system has never been sampled for PFAS. EPA's national monitoring covered systems serving 3,300 people or more, so no results exist — which is not evidence that none is present.
Who supplies water to Coleman? ▼
Coleman, City Of (PWSID FL6604861). Groundwater. Drawn from wells — SDWIS source code GW
When was this system last inspected? ▼
It was last inspected on 2024-12-20. No significant deficiencies were recorded.

What Should Coleman Residents Do?

1
Read your annual water report
Your supplier publishes a Consumer Confidence Report each July covering the prior year.
2
Check for a lead service line
Lead reaches tap water mainly through service lines and household plumbing. Suppliers now publish an inventory identifying lead lines.
3
Flush before drinking
If water has sat in pipes more than six hours, run the cold tap for two minutes before drinking or cooking.

Nearby Cities in Florida

The Villages, Fl Tap Water Quality 2026 Sumter Wildwood, Fl Tap Water Quality 2026 Sumter Lake Panasoffkee, Fl Tap Water Quality 2026 Sumter Bushnell, Fl Tap Water Quality 2026 Sumter Center Hill, Fl Tap Water Quality 2026 Sumter Webster, Fl Tap Water Quality 2026 Sumter